| Plan Review Notes For Permit 13120246 |
| Permit Number |
13120246 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2014-02-24 14:26:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. COMMENT FROM PREVIOUS REVIEWS: | | | | | | 4TH REVIEW - | | | | | | PER CONTRACTOR, DIRECT DECK PROPOSED. | | | | | | CONTRACTOR STILL NEEDS TO SELECT AN ASSEMBLY. FIRST | | | SUBMITTAL INDICATED AN ASSEMBLY WHICH HAD A DP | | | LIMITATION OF -90. | | | | | | 2ND SUBMITTAL HAD ENHANCED FASTENING FOR EXPOSURE C FOR | | | MECHANICALLY FASTENED. | | | | | | 3RD SUBMITTAL HAD A LETTER AND OTHER INFO REGARDING | | | DIRECT DECK, BUT CONTRACTOR HAS NOT YET SELECTED A | | | DIRECT DECK ASSEMBLY WHICH WILL MEET ***EXPOSURE D** | | | PRESSURES. ADDITIONALLY, THE ENGINEER'S CALCULATIONS | | | ARE BASED ON EXPOSURE C, BUT THIS PARCEL IS LOCATED IN | | | EXPOSURE D CONDITIONS, SEE FBC 2010 RESIDENTIAL 301. | | | | | | 4TH SUBMITTAL HAD A DETAIL (DRAWING). ON THE PRODUCT | | | APPROVAL, INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED | | | TO SHOW COMPLIANCE WITH FBC 2010 RESIDENTIAL 301. | | | | | | | | | |
|