Plan Review Notes
Plan Review Notes For Permit 13120246
Permit Number 13120246
Review Stop B
Sequence Number 4
Notes
Date Text
2014-02-24 14:26:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. COMMENT FROM PREVIOUS REVIEWS:
  
 4TH REVIEW -
  
 PER CONTRACTOR, DIRECT DECK PROPOSED.
  
 CONTRACTOR STILL NEEDS TO SELECT AN ASSEMBLY. FIRST
 SUBMITTAL INDICATED AN ASSEMBLY WHICH HAD A DP
 LIMITATION OF -90.
  
 2ND SUBMITTAL HAD ENHANCED FASTENING FOR EXPOSURE C FOR
 MECHANICALLY FASTENED.
  
 3RD SUBMITTAL HAD A LETTER AND OTHER INFO REGARDING
 DIRECT DECK, BUT CONTRACTOR HAS NOT YET SELECTED A
 DIRECT DECK ASSEMBLY WHICH WILL MEET ***EXPOSURE D**
 PRESSURES. ADDITIONALLY, THE ENGINEER'S CALCULATIONS
 ARE BASED ON EXPOSURE C, BUT THIS PARCEL IS LOCATED IN
 EXPOSURE D CONDITIONS, SEE FBC 2010 RESIDENTIAL 301.
  
 4TH SUBMITTAL HAD A DETAIL (DRAWING). ON THE PRODUCT
 APPROVAL, INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED
 TO SHOW COMPLIANCE WITH FBC 2010 RESIDENTIAL 301.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved