Plan Review Notes
Plan Review Notes For Permit 13120246
Permit Number 13120246
Review Stop B
Sequence Number 3
Notes
Date Text
2014-01-11 11:13:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. COMMENT FROM PREVIOUS REVIEWS:
  
 PROPOSED ASSEMBLY HIGHLIGHTED BY CONTRACTOR HAS AN
 ALLOWABLE DP OF -90. EXISTING DECK IS WOOD PLAN, DECK
 REQUIRED BY ASSEMBLY SELECTED IS PLYWOOD.
  
 3RD REVIEW -
  
 PER CONTRACTOR, DIRECT DECK PROPOSED, SO THE ENGINEER'S
 CALCULATIONS FOR ENHANCED FASTENING IS NOT REQUIRED.
  
 CONTRACTOR STILL NEEDS TO SELECT AN ASSEMBLY. FIRST
 SUBMITTAL INDICATED AN ASSEMBLY WHICH HAD A DP
 LIMITATION OF -90.
  
 2ND SUBMITTAL HAD ENHANCED FASTENING FOR EXPOSURE C FOR
 MECHANICALLY FASTENED.
  
 3RD SUBMITTAL HAD A LETTER AND OTHER INFO REGARDING
 DIRECT DECK, BUT CONTRACTOR HAS NOT YET SELECTED A
 DIRECT DECK ASSEMBLY WHICH WILL MEET ***EXPOSURE D**
 PRESSURES. ADDITIONALLY, THE ENGINEER'S CALCULATIONS
 ARE BASED ON EXPOSURE C, BUT THIS PARCEL IS LOCATED IN
 EXPOSURE D CONDITIONS, SEE FBC 2010 RESIDENTIAL 301.
  