| Plan Review Notes For Permit 13120246 |
| Permit Number |
13120246 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-12-21 14:14:31 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ENGINEERING IS NOT CONSISTENT WITH PROPOSED | | | CONSTRUCTION. ENGINEERING IS FOR SELF ADHERED ASSEMBLY, | | | NO ASSEMBLY NUMBER PROVIDED BUT ALLOWABLE DESIGN | | | PRESSURE IS -112 (ON ENGINEERING). | | | | | | PROPOSED ASSEMBLY HIGHLIGHTED BY CONTRACTOR HAS AN | | | ALLOWABLE DP OF -90. EXISTING DECK IS WOOD PLAN, DECK | | | REQUIRED BY ASSEMBLY SELECTED IS PLYWOOD. | | | |
|