Plan Review Notes For Permit 13120246
Permit Number 13120246
Review Stop B
Sequence Number 1
Notes
Date Text
2013-12-05 17:16:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ROOF FORM IS ILLEGIBLE. PLEASE SUBMIT LEGIBLE
 COPIES.
  
 2. SPECIFY TYPE OF WOOD DECK - PLYWOOD OR PLANK.
  
 3. PROPOSED DESIGN PRESSURES ARE NOT CLEAR BUT APPEAR
 TO BE 76.019 IN THE CORNER, PROVIDE CALCULATIONS.
 EXPOSURE WAS LEFT BLANK; THIS IS EXPOSURE D. IT IS NOT
 CLEAR HOW PRESSURES LOWER THAN EXPOSURE C HAVE BEEN
 DETERMINED. ZONE 3, EXPOSURE D, HAS A DP OF -127.3
 USING TABLES FBC RESIDENTIAL 2010 301.2(2), (3).
  
 4. DRAIN INSTALLATION REQUIRES A PLUMBING PERMIT.
 PROVIDE PLAN AND PERMIT APPLICATION.
  
  
  
  
  