| Plan Review Notes For Permit 13120155 |
| Permit Number |
13120155 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-02 17:30:37 | THE STATE OF FLORIDA HAS NOT YET ADOPTED THE 2011 | | | EDITION OF THE NEC, WE ARE CURRENTLY USING THE 2008 | | | EDITION | | | | | | ACCORDING TO THE SCOPE OF WORK AS DESCRIBED ON THE | | | PERMIT APPLICATION, THIS SYSTEM IS TO HAVE FULL VOICE | | | EVAC, YET THE SUBMITTAL PACKAGE DOES NOT INCLUDE DATA | | | SHEETS ON ANY PORTION THEREOF. FOR A SUCCESSFUL | | | ELECTRICAL PLAN REVIEW AS WELL AS FOR THE REQUIRED LOG, | | | A COMPLETE SET OF EQUIPMENT DATASHEETS SHALL BE | | | PROVIDED, INCLUDING THE BATTERIES. |
|