2014-07-11 12:12:53DATE: 7/11/2014
 PROJECT: SUMMA ST. GENERATOR
 PERMIT#: 13120147
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PROPOSED GENERATOR IS NOT CAPABLE OF SUSTAINING
 THE ENTIRE LOAD OF THE HOME, THEREFORE AN EMERGENCY
 SUB-PANEL SHALL BE PROVIDED IF THERE IS TO BE AN
 AUTOMATIC TRANSFER SWITCH. NEC 702.4(2)(B)
  
 2) THE ONE LINE DIAGRAM APPEARS TO BE INCOMPLETE. HOW
 DOES THE BALANCE OF THE HOME RECEIVE ELECTRICAL
 UTILITY? IS THERE ANOTHER PANEL INSIDE THE HOUSE? OR
 ARE THE BALANCE OF BRANCH CIRCUITS FED FROM THE "MAIN"
 PANEL? MORE INFORMATION REQUIRED. FBC 107.3.1.2
  
 3) LOAD CALCULATIONS, PANEL SCHEDULE AND SPECIFICATIONS
 SHALL BE PROVIDED FOR THE ATS/SUB-PANEL AND A PANEL
 SCHEDULE AND LOAD CALCULATION FOR THE "MAIN" PANEL. THE
 SUBMITTAL PACKAGE INCLUDES INFORMATION ON A LINE OF
 ATS'S BUT NOT A SPECIFIC ONE. THE LIST DOES NOT LIST
 ANY THAT ARE ALSO USED AS LOAD CENTERS. I NEED THE
 SPECIFIC MODEL NUMBER OF THE ATS/SUB-PANEL PROPOSED
 INDICATING THE CAPACITY TO INCLUDE A SUB-PANEL AS AN
 INTEGRAL PART OF THE EQUIPMENT AS INDICATED ON THE ONE
 LINE DIAGRAM. MORE INFORMATION REQUIRED. FBC 107.3.1.2
  