| Plan Review Notes For Permit 13120147 |
| Permit Number |
13120147 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-18 14:19:40 | THE PROPOSED GENERAUTOR IS NOT CAPABLE OF SUSTAINING | | | THE ENTIRE LOAD OF THE HOME, THEREFORE AS PROVIDED IN | | | NEC 702.4(2)(B) AND EMERGENCY SUB-PANEL SHALL BE | | | PROVIDED IF THERE IS TO BE AN AUTOMATIC TRANSFER | | | SWITCH. | | | THE FOLLOWING CORRECTIONS TO THE DRAWINGS SHALL BE | | | MADE: | | | 1. THE RISER DIAGRAM SHALL BE REVISED ACCORDINGLY. | | | 2. LOAD CALCS SHALL BE PROVIDED FOR THE EMERGENCY | | | SUB-PANEL | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|