2014-02-18 14:19:40THE PROPOSED GENERAUTOR IS NOT CAPABLE OF SUSTAINING
 THE ENTIRE LOAD OF THE HOME, THEREFORE AS PROVIDED IN
 NEC 702.4(2)(B) AND EMERGENCY SUB-PANEL SHALL BE
 PROVIDED IF THERE IS TO BE AN AUTOMATIC TRANSFER
 SWITCH.
 THE FOLLOWING CORRECTIONS TO THE DRAWINGS SHALL BE
 MADE:
 1. THE RISER DIAGRAM SHALL BE REVISED ACCORDINGLY.
 2. LOAD CALCS SHALL BE PROVIDED FOR THE EMERGENCY
 SUB-PANEL
  