| Plan Review Notes For Permit 13120147 |
| Permit Number |
13120147 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-14 16:03:35 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) NONE OF THE MODEL NUMBERS LISTED IN THE CONCRETE PAD | | | SCHEDULE CORRESPOND TO THE GENERAC MODEL 04390-3 | | | GENERATOR THAT IS TO BE INSTALLED. THE GENERATOR PAD | | | ENGINEERING IS VALID FOR ONE JOB AND IS REQUIRED TO | | | HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL, AS | | | STATED ON THE DOCUMENT. | | | | | | 2) PROVIDE ENGINEERING THAT SPECIFIES WINDSPEED, | | | EXPOSURE CATEGORY AND REQUIRED WIND LOAD PRESSURES AT | | | THE JOB LOCATION AND THE ATTACHMENT METHOD AND | | | FASTENERS THAT WILL BE USED TO ATTACH THE GENERATOR TO | | | THE PAD AND BE CAPABLE OF RESISTING THE WINLOADS. FBC | | | R301.2.1 | | | | | | 3) SUBMIT TWO COMPLETE SETS OF THE MANUFACTURER'S | | | INSTALLATION AND OWNER'S MANUAL. CITY AMENDMENTS | | | 107.2.1.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|