Plan Review Notes
Plan Review Notes For Permit 13120147
Permit Number 13120147
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-14 16:03:352010 FBC
  
 DENIED BY BUILDING
  
 1) NONE OF THE MODEL NUMBERS LISTED IN THE CONCRETE PAD
 SCHEDULE CORRESPOND TO THE GENERAC MODEL 04390-3
 GENERATOR THAT IS TO BE INSTALLED. THE GENERATOR PAD
 ENGINEERING IS VALID FOR ONE JOB AND IS REQUIRED TO
 HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL, AS
 STATED ON THE DOCUMENT.
  
 2) PROVIDE ENGINEERING THAT SPECIFIES WINDSPEED,
 EXPOSURE CATEGORY AND REQUIRED WIND LOAD PRESSURES AT
 THE JOB LOCATION AND THE ATTACHMENT METHOD AND
 FASTENERS THAT WILL BE USED TO ATTACH THE GENERATOR TO
 THE PAD AND BE CAPABLE OF RESISTING THE WINLOADS. FBC
 R301.2.1
  
 3) SUBMIT TWO COMPLETE SETS OF THE MANUFACTURER'S
 INSTALLATION AND OWNER'S MANUAL. CITY AMENDMENTS