| 2013-12-19 11:26:27 | 501 SOUTH FLAGLER DRIVE - #301 |
| | PERMIT #13120143 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET A-1.0: BOTH EXISTING STAIR TOWERS ARE OPEN TO THE |
| | SAME COMMON AREA (ELEVATOR "LOBBY") WHICH MAY RESULT IN |
| | BOTH STAIRS BEING COMPROMISED BY A SINGLE EVENT. PER |
| | NFPA 101 SECTION 7.5.1.3.5 IN EXISTING BUILDINGS, WHERE |
| | MORE THAN ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS |
| | REQUIRED, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| | SHALL BE EXEMPT FROM THE DIAGONAL MEASUREMENT |
| | SEPARATION DISTANCE CRITERIA OF 7.5.1.3.2 AND |
| | 7.5.1.3.3, PROVIDED THAT SUCH EXITS, EXIT ACCESSES, OR |
| | EXIT DISCHARGES ARE REMOTELY LOCATED IN ACCORDANCE WITH |
| | 7.5.1.3.1. PER NFPA 101 SECTION 7.5.1.3.1 WHERE MORE |
| | THAN ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, OR EXIT DISCHARGES SHALL BE |
| | REMOTELY LOCATED FROM EACH OTHER AND BE ARRANGED TO |
| | MINIMIZE THE POSSIBILITY THAT MORE THAN ONE HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY CONDITION. |
| | |
| | SHEET FA1.1: PROVIDE A FIRE ALARM NOTIFICATION |
| | APPLIANCE IN THE LARGE STORAGE ROOM (#103). |
| | |
| | FIRE SPRINKLER: FOR ISSUANCE OF A GENERAL BUILDING |
| | PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| | CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| | DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. AFTER THE BUILDING PERMIT |
| | HAS BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT |
| | SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |