| Plan Review Notes For Permit 13120138 |
| Permit Number |
13120138 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-26 17:33:43 | BECAUSE THIS EQUIPMENT WILL BE IN PLACE FOR AN EXTENDED | | | PERIOD YOU SHALL: | | | 1. PROVIDE A SITE DRAWING INDICATING THE LOCATION OF | | | BOTH THE TRANSFORMER AND THE EQUIPMENT REFLECTED ON THE | | | DRAWING. | | | 2. THIS APPARATUS IS NOT FREE STANDING, AND THEREFORE | | | YOU MUST SHOW HOW WILL THIS BE SUPPORTED. IF THIS IS TO | | | BE MOUNTED ON A POLE OR A SITE BUILT RACK, YOU MUST | | | PROVIDE ENGINEERED DRAWINGS SHOWING COMPLIANCE WITH | | | WIND LOADS. | | | 3. ALL RECEPTACLES SHALL BE GFCI PROTECTED AND COMPLY | | | WITH NEC 406.8. |
|