| Plan Review Notes For Permit 13120107 |
| Permit Number |
13120107 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-05 09:43:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS, FBC | | | R310, FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED | | | BY MORE THAN 5%. | | | | | | 2. IF THE PROPOSED NEW BEDROOM WINDOWS DO NOT COMPLY | | | WITH EMERGENCY ESCAPE AND RESCUE OPENING DIMENSIONS, | | | AND ANOTHER EXISTING EMERGENCY ESCAPE AND RESCUE | | | OPENING IS NOT PROVIDED, ALSO PROVIDE THE FOLLOWING | | | INFORMATION (FOR BEDROOMS ONLY); FBC R310, FBC EB | | | 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN | | | 5%: | | | | | | REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW | | | IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? | | | | | | REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING | | | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH | | | EXISTS WHEN THE WINDOW IS FULLY OPEN. | | | | | | REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING | | | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE | | | MANUFACTURER | | | |
|