| 2013-12-18 09:46:27 | BUILDING PLAN REVIEW |
| | PERMIT: 13120070 |
| | ADD: 1309 N FLAGLER DR. |
| | CONT: ATLANTIC GENERAL |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: DEC. 18/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) ARCHITECT JOSEPH B SHIVERS SEAL IS A 1 1/2 INCHES IN |
| | DIAMETER, PLEASE COMPLY WITH: |
| | 61G1-16.002 DESCRIPTION OF SEAL.11/11/13 |
| | (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE |
| | ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION |
| | NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR, |
| | AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE |
| | HEXAGONAL. . BOTH SEALS SHALL BE APPROXIMATELY 2" IN |
| | DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES |
| | SHALL APPEAR, AT THE TOP, THE WORDS "STATE OF FLORIDA" |
| | AND AT THE BOTTOM THE WORDS "REGISTERED ARCHITECT" OR |
| | "REGISTERED INTERIOR DESIGNER," WHICHEVER IS |
| | APPLICABLE. SEALS STATING "LICENSED INTERIOR DESIGNER," |
| | LAWFULLY OBTAINED BY REGISTERED INTERIOR DESIGNERS |
| | PRIOR TO JANUARY 1, 2014, MAY CONTINUE TO BE LAWFULLY |
| | USED |
| | |
| | 2) ALL OF THE ARCHITECTURAL SHEETS SIGNATURES ARE |
| | COPIES, PLEASE COMPLY WITH: |
| | PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE |
| | ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST |
| | AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC |
| | 61G1-16.003. FINAL OFFICIAL RECORD DOCUMENTS (NOT |
| | TRACINGS, ETC.) SHALL BE SO SIGNED. |
| | |
| | 3) THE STRUCTURAL SHEETS ARE ALL COPIES NOT THE |
| | ORIGINAL SIGNATURE. PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS EFFECTIVE DATE |
| | 05/06/2009 |
| | (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE |
| | SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL |
| | BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL |
| | ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | 4) SHEET A6.01 DOOR SCHEDULE NOTE # 4 INDICATES TO |
| | REFER TO RADIATION SHEILDING REPORT FOR LEAD LINED |
| | DOORS AND FRAMES, NOT INCLUDED IN THIS SUBMITTAL. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3 |
| | ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE |
| | DETAILS, COMPUTATIONS,, AND OTHER DATA NECESSARY TO |
| | DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE BASIS |
| | OF CALCULATIONS... |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |