| 2013-12-05 09:42:19 | FBC 2010 FUEL GAS REVIEW #1 | | | DENIED: | | | | | | 1. THE GAS PIPE APPEARS TO BE UNDERSIZED IF TABLE | | | 402.4(2) FOR METALLIC PIPE IS BEING USED. 3/4" @ 60' | | | ALLOWS 137,000 BTU | | | | | | 2. THE PLAN SHOWS A STOVE @ 10,000 BTU. A STANDARD COOK | | | TOP UNIT USES 40,000 BTU AND A STANDARD RANGE USES | | | 65,000 BTU PLEASE PROVIDE MANUFACTURE SHEETS IF STOVE | | | IS 10,000 BTU | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION: | | | | | | 1. OK | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | 4. OK | | | 5. OK | | | 6. NA | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | 8. NA | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2007 FUEL GAS SEC. 402.2 | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|