| Plan Review Notes For Permit 13120034 |
| Permit Number |
13120034 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-03 08:20:12 | BECAUSE THE SUBMITTED/APPROVED DRAWINGS DO NOT SPECIFY | | | WIRE SIZE AND INSULATION, NOR IS THERE A LOAD CALC FOR | | | THE CONNECTED LOAD, PRIOR TO FINAL INSPECTION AN 'AS | | | BUILT" DRAWING SHALL BE SUBMITTED FOR APPROVAL. A PANEL | | | SCHEDULE WILL BE REQUIRED FOR FINAL INSPECTION. | | | ALL WORK IS SUBJECT TO FIELD INSPECTOR'S APPROVAL |
|