| Plan Review Notes For Permit 13120028 |
| Permit Number |
13120028 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-09 18:42:07 | THIS REVIEW DENIED FOR LACK OF INFORMATION. | | | 1. NEED MORE DETAIL ON THE SCOPE AND/OR INTENT OF THIS | | | WORK. | | | 2. THE SUBMITTED PLAN & REVISION DO NOT MATCH.THE | | | REVISION INDICATES A FUTURE SERVICE AND THE PLANS | | | REFLECT THREE MAYBE FOUR FUTURE SERVICES. | | | 3. AT A MINIMUM IF THE INTENT IS TO CREATE THREE MAYBE | | | FOUR DIVIDED SPACES FOR FUTURE TENANT BUILD OUT, EACH | | | SPACE SHALL HAVE AT A MINIMUM A 100 AMP SERVICE WITH | | | ELECTRICAL PANEL, A WORKING LIGHT WITH SWITCH, AN | | | EMERGENCY LIGHT ALL OF WHICH SHALL BE COMPLIANCE WITH | | | THE FBC-ENERGY CONSERVATION SECTION 501.2 | | | 4. AS PER NEC 110.16 ARC-FLASH PROTECTION LABELS SHALL | | | BE REQUIRED. | | | 5. MISSING DISCONNECT AND WIRING DETAIL FOR THE | | | CONDENSING UNIT. | | | 6. AS PER NEC 210.63, A SERVICE OUTLET IS REQUIRED | | | WITHIN 25 FT. OF THE CONDENSING UNIT, NOT ONE SHOWN ON | | | PLANS. |
|