| Plan Review Notes For Permit 13120015 |
| Permit Number |
13120015 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-13 09:23:33 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) THE ELECTRICAL PANEL LOCATED NEXT TO THE KITCHEN | | | SINK IS REQUIRED TO BE RE-LOCATED (IT CAN BE REVERSED | | | TO FACE TOWARD THE LIVING ROOM). NEC 240.24(A) | | | | | | 2) AN ELECTRICAL RECEPTACLE OUTLET IS REQUIRED WITHIN | | | 25 FEET OF EACH A/C CONDENSERS FOR SERVICE. NEC 210.63 | | | | | | 3) THE BATHROOM AND KITCHEN RECEPTACLES SERVICING THE | | | COUNTERTOPS ARE REQUIRED TO BE GFCI PER NEC 210.8. | | | | | | 4) RECEPTACLE OUTLET SPACING IN THE UNITS IS REQUIRED | | | TO COMPLY WITH NEC 210.52. | | | | | | 5) TAMPER RESISTANT RECEPTACLES ARE REQUIRED PER NEC | | | 406.11. | | | | | | 6) AFCI PROTECTION IS REQUIRED PER 210.12. | | | | | | 7) THE REQUIRED SMOKE ALARM IS NOT SHOWN FOR THE NEWLY | | | CREATED BEDROOM. FBC R314. | | | | | | NOTE: PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW | | | EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|