| 2014-01-13 14:01:35 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PLANS INDICATE THAT THIS IS AN EXISTING TWO - |
| | FAMILY DWELLING. THE EXISTING FLOOR PLAN IS UNCLEAR |
| | ABOUT THE LOCATION OF THE SEPARATION WALL BETWEEN THE |
| | TWO UNITS. THE PROPOSED FLOOR PLAN SHOWS THAT NEW WALLS |
| | ARE BEING INSTALLED THAT WILL RECONFIGURE THE TWO |
| | SPACES AND CHANGE THE LOCATION OF THE DEMISING WALL. |
| | FBC R302.3 REQUIRES THE TWO DWELLING UNITS TO BE |
| | SEPARATED FROM EACH OTHER BY A ONE HOUR FIRE-RESISTANCE |
| | RATED WALL ASSEMBLY. THE FIRE RATED WALL ASSEMBLY IS |
| | REQUIRED TO EXTEND TO AND BE TIGHT AGAINST THE EXTERIOR |
| | WALL AND EXTEND FROM THE FOUNDATION AND BE TIGHT |
| | AGAINST THE UNDER SIDE OF THE ROOF SHEATHING. DESIGNATE |
| | THIS WALL ON THE FLOOR PLAN AND PROVIDE A WALL ASSEMBLY |
| | DETAIL WITH THE UL LISTING NUMBER FOR IT. |
| | |
| | 2) IT APPEARS THAT A NEW BEDROOM WITH A CLOSET HAS BEEN |
| | CREATED IN THE UNIT ON THE LEFT. FBC R310 REQUIRES |
| | EVERY SLEEPING ROOM TO HAVE AT LEAST ONE EMERGENCY |
| | ESCAPE AND RESCUE OPENING. PLEASE SHOW COMPLIANCE. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R314 FOR SMOKE ALARMS IN |
| | SLEEPING ROOMS. |
| | |
| | 4) PROVIDE AN EXTERIOR WALL SECTION FOR THE " IN-FILL" |
| | AT THE SLIDING GLASS DOOR THAT SPECIFIES THE INTERIOR |
| | FINISH, THE INSULATION, THE WATER RESISTIVE BARRIER AND |
| | THE EXTERIOR WALL FINISH. CITY AMENDMENTS 107.2.1 |
| | |
| | 5) THE VALUE SPECIFIED ON THE APPLICATION APPEARS TO BE |
| | LOW FOR THE SCOPE OF WORK SPECIFIED. PLEASE INCLUDE THE |
| | COSTS OF ALL MATERIAL, LABOR AND DESIGN COSTS FOR ALL |
| | TRADES, AS WELL AS, PROFIT AND OVERHEAD. CITY |
| | AMENDMENTS 109.3 |
| | |
| | 6) THE PLANS INDICATE THAT AN EXISTING ENCLOSED FRONT |
| | PORCH AREA OF 96 SQFT IS BEING CONVERTED TO LIVING |
| | AREA. THIS WILL REQUIRE ONE SET OF THE APPROVED PLANS |
| | TO BE REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF ANY |
| | IMPACT FEES ARE DUE. |
| | |
| | 7) SEPARATE PERMITS ARE REQUIRED FOR THE DRIVEWAYS AND |
| | APPROACH APRONS. |
| | |
| | NOTE: PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW |
| | EACH OF THE PLAN REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |