| 2014-01-10 16:46:40 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER TO PROVIDE DESIGN CRITERIA AS REQUIRED BY |
| | SEC. R301 OF 2010 FBC-RESIDENTIAL. SPECIFY BUILDING |
| | CODE, EXPOSURE, WIND LOADS, ETC. AND REVISE THE WINDOWS |
| | DESIGN PRESSURES. ACCORDING TO SEC. R301.2.1.4.3 OF |
| | 2010 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN |
| | EXPOSURE "D". DESIGN PRESSURES SHOWN ON PLANS DON'T |
| | CORRESPOND TO EXPOSURE "D". REVISE AS REQUIRED. |
| | |
| | 2- SCOPE OF WORK IN PERMIT APPLICATION IS TO REPLACE |
| | EXISTING AWNING WINDOWS WITH IMPACT RESISTANCE WINDOWS |
| | (12 TOTAL). MIAMI-DADE NOA 12-0906.06 SUBMITTED IS FOR |
| | NON-IMPACT SINGLE HUNG WINDOWS. CLARIFY AS REQUIRED. |
| | ***NOTE; WINDOWS NEED TO HAVE HURRICANE IMPACT |
| | PROTECTION AS REQUIRED BY SEC. R301.2.1.2. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) IMPACT WINDOWS AS SPECIFIED ON PERMIT APPLICATION. |
| | (NOTE: VERIFY DESIGN PRESSURES WITH ENGINEER REVISED |
| | DESIGN PRESSURES AS REQUIRED BY ITEM #1 ABOVE). |
| | |
| | B) HURRICANE SHUTTERS IF WINDOWS TO BE INSTALLED HAVE |
| | NOT IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE . SEE CITY HURRICANE SHUTTERS INSTALLATION |
| | SCHEDULE SAMPLE. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 5- SPECIFY SAFETY GLASS FOR WINDOWS LOCATED IN MASTER |
| | BATHROOM AND GUEST BATHROOM AS REQUIRED BY SEC. R308.4. |
| | |
| | 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS TO FBC. REVISE |
| | AS REQUIRED. |
| | |
| | ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |