| 2013-12-18 16:28:33 | BUILDING PLAN REVIEW |
| | REVISION: 13110894 |
| | PERMIT: 13090504 |
| | ADD: 460 S ROSEMARY AVE # 180 |
| | CONT: DAKENNA |
| | TEL: (561)856-6655 NEYITA |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 18/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A8.2 IDENTIFIES THE SHAFT WALL ASSEMBLY (SW-2) |
| | AS A UL LISTED U415. PLEASE PROVIDE THE ACTUAL LSITING |
| | SHEET WITH COMPONENTS SINCE THE FIELD INSPECTOR DOES |
| | NOT HAVE A UL BOOK IN THE FIELD. |
| | |
| | 2) A8.2 WHERE THE SHAFT STARTS ON THE SECOND FLOOR THE |
| | PLANS DO NOT PROVIDE A ENCLOSURE AT THE BOTTOM OF THE |
| | SHAF TAS PER 2010 FBC-B 708.11. THE 2010MECHANICAL CODE |
| | 506.3.10. IS MORE SPECIFIC TO GREASE DUCT ENCLOSURES |
| | AND THE DUCT ENCLOSURE SHALL HAVE NOT LESS THAN THE |
| | FLOOR ASSEMBLY IT PENETRATES. |
| | |
| | 3) SHEET A8.2 PLEASE PROVIDE THE CLEARENCE BETWEEN THE |
| | GREASE DUCT AND SHAFT WALL ASSEMBLY PROVIDE COMPLIANCE |
| | WITH MECHANICAL 506.3.10.1. |
| | |
| | 4) THE ROOFTOP EQUIPMENT AND ANCHORING OF EQUIPMENT IS |
| | TO BE UNDER SEPERATE PERMIT, THIS PERMIT SHOULD BE |
| | TRAVELING ALONG WITH THIS PERMIT TO MAKE A COMPLETE |
| | PACKAGE. |
| | |