| 2013-12-13 13:02:13 | 217 BUTLER STREET - UNIT #9 | | | PERMIT #13110875 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | **CHANGE OF OCCUPANCY FROM BUSINESS TO APARTMENT** | | | | | | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE | | | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 | | | OF NFPA 101 FLORIDA EDITION 2009. FOR NON-SEPARATED | | | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE | | | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO | | | THE BUILDING. | | | | | | PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, | | | FIRE RATED WALLS, EXITS, EGRESS WINDOWS, TRAVEL | | | DISTANCES, ETC. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PER NFPA 101 SECTION 30.3.5 ALL NEW APARTMENTS SHALL BE | | | PROTECTED BY AN AUTOMATIC AND SUPERVISED SPRINKLER | | | SYSTEM. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|