| Plan Review Notes For Permit 13110860 |
| Permit Number |
13110860 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-06 15:06:47 | THOUGH THIS IS A DECORATIVE FOUNTAIN, IT MUST COMPLY | | | WITH SECTION 1 & V OF NEC 680, THEREFORE ALL | | | UNDERGROUND ELECTRICAL CONDUIT IF NOT DIRECTLY | | | ASSOCIATED WITH THE FOUNTAIN SHALL BE RE-ROUTED TO | | | MAINTAIN A MINIMUM OF 5 FT CLEARANCE FORM THE FOUNTAIN. |
|