| Plan Review Notes For Permit 13110814 |
| Permit Number |
13110814 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-01-16 14:16:28 | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | THE GENERATOR SPECS INDICATE NG CONSUMPTION AT 359 | | | FT3/HR. SHEET P0.1 INDICATES A 250' LONG, 1" PIPE WHICH | | | ONLY SUPPLIES 119. SPOKE TO GORDON MEYERS OF KAMM. HE | | | IS TO REEVALUATE. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|