| Notes |
| Date |
Text |
| 2013-12-10 18:51:22 | THE FOLLOWING CORRECTIONS NEED TO BE MADE FOR THE NEXT | | | PLAN REVIEW: | | | 1.PROVIDE COMPLETE LITERATURE PACKAGE FOR GENERATOR AND | | | TRANSFER GEAR. | | | 2. SHOW ELEVATIONS FOR THE METER ROOM IF INTENTIONS ARE | | | TOP PLACE PANEL 6G BELOW EXISTING PANEL L2C | | | 3. INCLUDE A COMPLETE LEGEND FOR BETTER UNDERSTANDING | | | OF YOUR RISER DIAGRAM | | | 4. PROVIDE LOAD CALC & A PANEL SCHEDULE FOR PANEL H6 | | | 5. CORRECT THE NOMENCLATURE FOR THE TRANSFORMER, OR | | | EXPLAIN WHAT A SINGLE PHASE TRANSFORMER IS DOING THERE. | | | 6. COMPLETE THE RISER DIAGRAM FOR THE PENTHOUSE LEVEL. |
|