| Plan Review Notes For Permit 13110814 |
| Permit Number |
13110814 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-12 09:21:54 | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | PROVIDE DETAILS TO INDICATE THE METHOD INTENDED TO | | | INSTALL OR SECURE THE THE GENERATOR TO THE STRUCTURE. | | | PROVIDE MINMUM STRUCTURE DETAILS RELATED TO METHOD OF | | | ATTACHMENT AND CAPACITY TO HANDLE CONCENTRATED LOAD OF | | | EQUIPMENT. PROVIDE DETAIL FOR NECESSARY PENETRATIONS OF | | | STRUCTURE TO RUN GAS PIPING AND FIRESTOPPING DETAILS | | | AND MAY BE NEEDED. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | | | 2013-12-10 18:56:13 | ELECTRIC PLACED ON SAK DESK |
|