| Notes |
| Date |
Text |
| 2013-12-04 12:41:41 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) SHOW THAT THE NEW POOL WILL COMPLY WITH 2008 NEC | | | 680.8 OVERHEAD CONDUCTOR CLEARANCES AND 680.10 | | | UNDERGROUND WIRING LOCATION. | | | | | | 2) GENERAL NOTE 8 ON PLAN SHEETS 1,2 & 3 AND THE | | | BONDING NOTE ON SHEET 3, INCORRECTLY REFERENCE THE 2011 | | | NEC. THE 2008 NEC APPLIES TO THIS PERMIT. PLEASE | | | CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|