Plan Review Notes
Plan Review Notes For Permit 13110778
Permit Number 13110778
Review Stop Z
Sequence Number 1
Notes
Date Text
2014-03-12 09:57:27FAILED
  
 1) THE PLACEMENT OF THE NEW GENERATOR, PAD, ENCLOSURE
 AND THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT
 BUILDING IS A MODIFICATION TO THE APPROVED SITE AND
 LANDSCAPE PLANS AND REQUIRES A MINOR PLANNED
 DEVELOPMENT AMENDMENT.
  
 2) PLEASE BE AWARE THAT THIS IS A POSSIBLE LOCATION FOR
 THE RELOCATION OF THE PACE BUS PARKING ONCE TRADITIONS
 PHASE II IS CONSTRUCTED. STAFF RECOMMENDS TAKING INTO
 ACCOUNT THE FUTURE PARKING RELOCATION WHEN PLANNING ANY
 NEW SITE FACILITIES.
  
 3) ANY TREE RELOCATION REQUIRES A TREE ALTERATION
 PERMIT.
  
 4) LANDSCAPE IS REQUIRED TO SCREEN THE GENERATOR AND
 THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT
 BUILDING. A LANDSCAPE PERMIT IS REQUIRED.
  
 5) THE GENERATOR SHALL BE SCREENED WITH AN OPAQUE
 FENCE/WALL FOR THE FULL HEIGHT OF THE GENERATOR. A
 FENCE PERMIT IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
2014-02-18 15:12:392/18/14