2013-12-30 13:27:48PERMIT #13110759
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
  
 PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 PROVIDE AN 8 INCH TALL STEEL BAFFLE OR PROVIDE 16
 INCHES OF SPACE BETWEEN THE DEEP FAT FRYER AND SURFACE
 FLAMES OF THE ADJACENT EQUIPMENT.
  
  