| 2014-03-21 13:35:57 | |
| | ***REVIEW IN PROGRESS... |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) HARDIEPLANK SIDING AS SHOWN ON PLANS. |
| | ***NOA 07-0418.04 SUBMITTED EXPIRED ON MAY 01, 2012. |
| | NEED CURRENT NOA. |
| | |
| | B) HORIZONTAL SLIDER WINDOWS AS SHOWN IN THE NEW |
| | KITCHEN AREA. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | |
| | |
| | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 3- SHEET 2 OF 3: |
| | A) THE COMPONENTS AND CLADDING DESIGN PRESSURES SHOWN |
| | FOR THE ROOF ARE INCORRECT. REVISE AS REQUIRED. SEE |
| | TABLE R301.2(2) OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP |
| | IN MIND THAT THIS TABLE IS FOR EXPOSURE "B". NEED TO |
| | ADJUST TO EXPOSURE "C" ACCORDINGLY. |
| | *** REVISED VALUES ARE INCORRECT. WORST CASE SCENARIO |
| | IS FOR ROOF ZONE #3. PROVIDE CALCULATIONS. SEC. |
| | 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | 4- SECTION B-B ON SHEET 3 OF 3: |
| | A) NEED GUTTERS AS REQUIRED BY SEC. R318.6. |
| | ***PROVIDE COMPLETE INFORMATION. EXTERIOR REAR |
| | ELEVATION DOESN'T SHOW THE DOWNSPOUTS. |
| | |
| | 5- NEW COMMENT: INSULATION CHANGED FROM BATT INSULATION |
| | TO ICYNENE INSULATION. PROVIDE ICYNENE ICC EVALUATION |
| | REPORT AND MANUFACTURER SPECS. |
| | |
| | 6- ARCHITECT TO REVISE THE ENERGY CALCULATIONS (FORM |
| | 402-2010 SUBMITTED THIS TIME) AND COORDINATE WITH FLOOR |
| | PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION: |
| | ***NOTES: |
| | A) CAREFULLY READ ALL THE GENERAL INSTRUCTIONS ON PAGE |
| | ONE AND ALL THE NOTES ON PAGE TWO. THEY SHOW ALL THE |
| | CONDITIONS THAT NEED TO BE MET IN ORDER TO USE THIS |
| | FORM. AND REVISE ACCORDINGLY. |
| | |
| | B) TOTAL ADDITION APPLIES TO THE NEW KITCHEN AREA AND |
| | THE AREA ENCLOSED BY THE PARTIALLY COVERED PORCH. TAKE |
| | THIS INTO CONSIDERATION FOR THE TOTAL ADDITION |
| | CONDITIONED AREA. THE NEW KITCHEN IS LOCATED IN AN |
| | EXISTING ENCLOSED PORCH. THIS AREA WAS NOT INSULATED. |
| | NEED TO INSULATE THE RAISED FLOOR, WALLS AND CEILING IN |
| | THIS AREA. |
| | |
| | |
| | |
| | ***NOTE: |
| | PLEASE PROVIDE A RESPONSE LETTER SHOWING HOW AND WHERE |
| | EACH COMMENT WAS ADDRESSED TO EXPEDITE THE REVIEW |
| | PROCESS. |
| | |