| 2013-11-21 14:36:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC 2010 RESIDENTIAL 301, FBC R 801.2, NOT CLEAR HOW | | | LOAD PATH WILL BE MAINTAINED WITH SUCH A SMALL PORTION | | | OF THE ROOF RAFTER BEARING ON TO THE TIE BEAM. PROVIDE | | | CALCULATIONS OR MORE INFORMATION. | | | | | | 2. FBC 107, SHOW HOW MOISTURE ISSUES (CONCRETE TO | | | UNTREATED LUMBER) WILL BE ADDRESSED. | | | | | | 3. PLAN SHOWS THAT ROOF TRUSSES WILL BE REPLACED BY | | | ROOF RAFTERS, NOT CLEAR HOW THIS WILL BE ACCOMPLISHED, | | | FBC 107. HOW CAN ONE SIDE O THE MEMBER BE A TRUSS, AND | | | THE OTHER A RAFTER? OW DOES THE TRUSS TIE IN TO THE | | | RIDGE BEAM? | | | | | | | | | |
|