Plan Review Notes
Plan Review Notes For Permit 13110691
Permit Number 13110691
Review Stop B
Sequence Number 3
Notes
Date Text
2014-02-09 13:34:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE SAME INSTALLATION SCHEUDLE DATED 1/3 WAS SUBMITTED.
 ALL COMMENTS FROM PREVIOUS REVIEW WERE IN REGARDS TO
 THE INSTALLATIN SCHEDULE. AS SAME INFORMATION WAS
 RESUBMITTED, COMMENTS REMAIN THE SAME. FOR YOUR
 CONVENIENCE, THE COMMENTS ARE AS FOLLOWS:
  
 1. SHUTTER CONNECTION MOUNTING TYPE PROPOSED NOT CLEAR.
 TOP IS 6B, SEE SHEET 6, NO 6B. SECTION 6 IS FOR POURED
 CONCRETE, INSTALLATION SCHEDULE STATES TOP SUBSTRATE IS
 WOOD.
  
 2. ANCHOR SPACING DOES NOT APPEAR TO COMPLY WITH
 REQUIREMENTS OF PRODUCT APPROVAL. 12", 1, TOP CIRCLED
 ON SHEET 5, 3" EDGE DISTANCE. SEE FACTOR CHART ON SHEET
 5; THIS REQUIRES A .35 FACTOR APPLIED TO THE ANCHOR
 SPACING (12" X .35). THIS CHART IS FOR CONCRETE
 SUBSTRATE, INSTALLATION SCHEDULE STATES TOP IS WOOD.
 PLEASE CORRELATE.
  
 ALSO CIRCLED IS 11", 8, BOTTOM; 12" PROPOSED. IT
 APPEARS THAT, WITH A 3" EDGE DISTANCE, ANCHOR SPACING
 TO BE 11" X .35.
  
 3. THE 8' OR LESS CHART WAS USED, SHEET 5, BUT THE SPAN
 STATED IS 110". SPAN SHOULD BE MEASURED ANCHOR TO
 ANCHOR, WHICH SHOULD BE 116" FOR A 110" OPENING WITH 3"
 EDGE DISTANCE TOP AND BOTTOM. REVISE.
  
  
  