| Plan Review Notes For Permit 13110691 |
| Permit Number |
13110691 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-02-09 13:34:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THE SAME INSTALLATION SCHEUDLE DATED 1/3 WAS SUBMITTED. | | | ALL COMMENTS FROM PREVIOUS REVIEW WERE IN REGARDS TO | | | THE INSTALLATIN SCHEDULE. AS SAME INFORMATION WAS | | | RESUBMITTED, COMMENTS REMAIN THE SAME. FOR YOUR | | | CONVENIENCE, THE COMMENTS ARE AS FOLLOWS: | | | | | | 1. SHUTTER CONNECTION MOUNTING TYPE PROPOSED NOT CLEAR. | | | TOP IS 6B, SEE SHEET 6, NO 6B. SECTION 6 IS FOR POURED | | | CONCRETE, INSTALLATION SCHEDULE STATES TOP SUBSTRATE IS | | | WOOD. | | | | | | 2. ANCHOR SPACING DOES NOT APPEAR TO COMPLY WITH | | | REQUIREMENTS OF PRODUCT APPROVAL. 12", 1, TOP CIRCLED | | | ON SHEET 5, 3" EDGE DISTANCE. SEE FACTOR CHART ON SHEET | | | 5; THIS REQUIRES A .35 FACTOR APPLIED TO THE ANCHOR | | | SPACING (12" X .35). THIS CHART IS FOR CONCRETE | | | SUBSTRATE, INSTALLATION SCHEDULE STATES TOP IS WOOD. | | | PLEASE CORRELATE. | | | | | | ALSO CIRCLED IS 11", 8, BOTTOM; 12" PROPOSED. IT | | | APPEARS THAT, WITH A 3" EDGE DISTANCE, ANCHOR SPACING | | | TO BE 11" X .35. | | | | | | 3. THE 8' OR LESS CHART WAS USED, SHEET 5, BUT THE SPAN | | | STATED IS 110". SPAN SHOULD BE MEASURED ANCHOR TO | | | ANCHOR, WHICH SHOULD BE 116" FOR A 110" OPENING WITH 3" | | | EDGE DISTANCE TOP AND BOTTOM. REVISE. | | | | | | | | | |
|