| Notes |
| Date |
Text |
| 2013-12-10 19:35:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 2010 | | | RESIDENTIAL 301. | | | | | | 2. PLAN TO INCLUDE PRINTED NAME AND SIGNATURE OF | | | INDIVIDUAL TAKING RESPONSIBILITY FOR THE PLAN FBC 107. | | | | | | 3. PLANS DO NOT SHOW ANY STEEL REINFORCEMENT. PROVIDE | | | CALCULATIONS FBC 2010 RESIDENTIAL 301. | | | | | | 4. VALUE IS TO INCLUDE LABOR AND MATERIALS, OVERHEAD | | | AND PROFIT FBC 109. PROVIDE A REASONABLE VALUATION. | | | | | | |
|