Plan Review Notes
Plan Review Notes For Permit 13110669
Permit Number 13110669
Review Stop Z
Sequence Number 1
Notes
Date Text
2013-12-10 10:59:09FAILED
  
 1) THE REAR WALL ON THE PERMIT SHOWS THAT THERE IS AN
 ADDITIONAL DOOR FROM THE LANDLORD APPROVED SHELL
 BUILDING. EITHER PROVIDE CONSTRUCTION PLANS FOR THE
 ADDITIONAL DOOR WITH THIS PERMIT, PROVIDE A SEPARATE
 PERMIT FOR THE WORK OR PROVIDE A LETTER FROM THE
 LANDLORD THAT THEY WILL BE REVISING THEIR PLANS AND
 DOING THE WORK. THERE IS A NOTE ON PLANS STATING THE
 WORK WILL BE DONE BY OTHERS.
  
 2) THE PROPOSED FRONT EXTERIOR ELEVATION DOES NOT MATCH
 THE SUBMITTED PLANS. THE LANDLORD PLANS SHOW AN AWNING
 OVER THE STOREFRONT, WHICH IS WHERE THE SUBMITTED PLANS
 SHOW THE SIGN. THE REAR ELEVATION IS ALSO INCORRECT
 BASED ON THE ONE VS. TWO DOORS. THE ELEVATIONS SHALL
 EITHER BE CORRECTED TO MATCH THE APPROVED SHELL
 ELEVATIONS OR PROVIDE A LETTER FROM THE LANDLORD
 STATING THE SHELL PERMIT WILL BE REVISED.
  
 3) PLEASE VERIFY THE RTU DATA. THE LANDLORD PLANS SHOW
 RTU-1 AS 12.5 TONS AND RTU-2 AS 6 TONS.
  
 4) PLEASE NOTE THAT ALL SIGNAGE REQUIRES A SEPARATE
 PERMIT.
  