| Plan Review Notes For Permit 13110608 |
| Permit Number |
13110608 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-12-09 09:06:12 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FS471. | | | | | | 2. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FS481. | | | | | | 3. SEE FBC 1603.1.4 AND INCLUDE REQUIRED INFORMATION | | | FOR WIND DESIGN CRITERIA. WIND DESIGN CRITERIA NOT | | | CLEAR AS IT STATES THAT THIS COMPLIES WITH ASCE 7-10 | | | AND FBC 2010, 146MPH. THIS PARCEL IS LOCATED IN 170MPH | | | ULTIMATE. | | | | | | 4. THIS PARCEL IS LOCATED IN EXPOSURE C, FBC 1609, | | | REVISE PLAN. | | | | | | 5. NOTES MAKE REFERENCE TO A RESIDENTIAL BUILDING, BUT | | | PAPA RECORDS SHOW A COMMERCIAL BUILDING AT THIS | | | LOCATION. | | | | | | 6. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED | | | FOR ALL COMPONENTS & CLADDING, FAC9N-3. THEY ARE TO BE | | | REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL FBC | | | 107. | | | | | | | | | |
|