Plan Review Notes
Plan Review Notes For Permit 13110591
Permit Number 13110591
Review Stop B
Sequence Number 3
Notes
Date Text
2014-02-09 13:51:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 1. PRODUCT APPROVAL SUBMITTED IS ILLEGIBLE. THERE IS A
 LINE THROUGH FASTENER TYPE. ONLY ONE SET SUBMITTED.
 PROVIDE TWO LEGIBLE SETS OF PRODUCT APPROVALS. FBC 107.
  
 2. SEE SHEET 6, ANCHOR CHART. TAP CON CANNOT BE USED
 FOR WALL MOUNT TYPE 8.
  
 3. ALTHOUGH IT IS ACCEPTABLE TO EXCEED CODE COMPLIANCE,
 IT IS NOT CLEAR WHY A DP OF -76 HAS BEEN STATED FOR
 THIS JOB. -45.8 PSF IS WORST CASE FOR ZONE 4, 10SF,
 25'MRH. ZONE 5 WORST CASE, SAME CONDITIONS, IS -56.6.
 SEE FBC 2010 RESIDENTIAL TABLE 301.2(2) AND (3).
  
  