| Plan Review Notes For Permit 13110591 |
| Permit Number |
13110591 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-02-09 13:51:14 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | 1. PRODUCT APPROVAL SUBMITTED IS ILLEGIBLE. THERE IS A | | | LINE THROUGH FASTENER TYPE. ONLY ONE SET SUBMITTED. | | | PROVIDE TWO LEGIBLE SETS OF PRODUCT APPROVALS. FBC 107. | | | | | | 2. SEE SHEET 6, ANCHOR CHART. TAP CON CANNOT BE USED | | | FOR WALL MOUNT TYPE 8. | | | | | | 3. ALTHOUGH IT IS ACCEPTABLE TO EXCEED CODE COMPLIANCE, | | | IT IS NOT CLEAR WHY A DP OF -76 HAS BEEN STATED FOR | | | THIS JOB. -45.8 PSF IS WORST CASE FOR ZONE 4, 10SF, | | | 25'MRH. ZONE 5 WORST CASE, SAME CONDITIONS, IS -56.6. | | | SEE FBC 2010 RESIDENTIAL TABLE 301.2(2) AND (3). | | | | | | |
|