Plan Review Notes
Plan Review Notes For Permit 13110586
Permit Number 13110586
Review Stop P
Sequence Number 1
Notes
Date Text
2013-12-26 16:03:22NEW SINGLE FAMILY RESIDENCE (R3), PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM TO MATCH ACTUAL FLOOR
 PLAN LAYOUT. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- REVISE CLOTHES WASHER DISCHARGE. APPLIANCES WITH
 PUMPING ACTION DISCHARGE CAN'T BE CONNECTED AS SHOWN.
 SEC. P3005.1.1 OF 2010 FBC-RESIDENTIAL.
  
 3- SOME FIXTURES ARE MISSING THE DRAIN PIPE SIZE.
 SPECIFY THE DRAIN SIZE OF EACH FIXTURE AS REQUIRED BY
 SEC. P3005.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712