| Plan Review Notes For Permit 13110586 |
| Permit Number |
13110586 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-26 16:03:22 | NEW SINGLE FAMILY RESIDENCE (R3), PLUMBING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISE PLUMBING RISER DIAGRAM TO MATCH ACTUAL FLOOR | | | PLAN LAYOUT. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 2- REVISE CLOTHES WASHER DISCHARGE. APPLIANCES WITH | | | PUMPING ACTION DISCHARGE CAN'T BE CONNECTED AS SHOWN. | | | SEC. P3005.1.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- SOME FIXTURES ARE MISSING THE DRAIN PIPE SIZE. | | | SPECIFY THE DRAIN SIZE OF EACH FIXTURE AS REQUIRED BY | | | SEC. P3005.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|