Plan Review Notes
Plan Review Notes For Permit 13110586
Permit Number 13110586
Review Stop M
Sequence Number 1
Notes
Date Text
2013-12-26 16:02:57NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- CLARIFY WHY SUBMITTING TWO DIFFERENT EQUIPMENT
 SIZING CALCULATIONS. PROVIDE ONLY ONE. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 2- CALCULATIONS DONE BY APOLLO AIR:
 A) EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS SUBMITTED DON'T MATCH EQUIPMENT SHOWN ON
 THE A/C PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) REVISE DESIGN DATA ON PAGE 2. THE REFERENCE CITY IS
 WEST PALM BEACH, NOT FORT LAUDERDALE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- MECHANICAL PLAN SUBMITTED:
 A) PERSON RESPONSIBLE FOR THE DESIGN NEED TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 B) REVISE GENERAL MECHANICAL NOTE #6. DOOR NEEDS AT
 LEAST 1", NOT 3/4" UNDERCUT AS REQUIRED BY SEC. M1602.4
 OF 2010 FBC-RESIDENTIAL.
  
 C) NEED AT LEAST 12" TRANSFER DUCT SIZE FOR GUEST SUITE
 AS REQUIRED BY SEC. M1602.4. REVISE AS REQUIRED.
  