| Plan Review Notes For Permit 13110586 |
| Permit Number |
13110586 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-26 16:02:57 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- CLARIFY WHY SUBMITTING TWO DIFFERENT EQUIPMENT | | | SIZING CALCULATIONS. PROVIDE ONLY ONE. SEC. 103.2.2 OF | | | 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- CALCULATIONS DONE BY APOLLO AIR: | | | A) EQUIPMENT LISTED ON THE EQUIPMENT SIZING | | | CALCULATIONS SUBMITTED DON'T MATCH EQUIPMENT SHOWN ON | | | THE A/C PLANS. REVISE AS REQUIRED TO MATCH. SEC. | | | 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | B) REVISE DESIGN DATA ON PAGE 2. THE REFERENCE CITY IS | | | WEST PALM BEACH, NOT FORT LAUDERDALE. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 3- MECHANICAL PLAN SUBMITTED: | | | A) PERSON RESPONSIBLE FOR THE DESIGN NEED TO PROVIDE | | | NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | B) REVISE GENERAL MECHANICAL NOTE #6. DOOR NEEDS AT | | | LEAST 1", NOT 3/4" UNDERCUT AS REQUIRED BY SEC. M1602.4 | | | OF 2010 FBC-RESIDENTIAL. | | | | | | C) NEED AT LEAST 12" TRANSFER DUCT SIZE FOR GUEST SUITE | | | AS REQUIRED BY SEC. M1602.4. REVISE AS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|