2013-12-12 15:47:22THIS APPLICATION IS CONDITIONALLY APPROVED PROVIDED
 THAT COMPLIANCE WITH THE HEREIN DESCRIBED IS OBSERVED:
 1. AS PER NEC 680.71, THE OUTLET FOR THE HYDROMASSAGE
 TUB SHALL BE GFCI PROTECTED.
 2. AS PER FBC-R315, CARBON MONOXIDE DETECTORS SHALL BE
 INSTALLED
 3. THOUGH NOT INDICATED ON THE DRAWINGS, COMPLIANCE
 WITH FBC-E404.1 SHALL BE REQUIRED.
 4. ALL WORK SHALL COMPLY WITH ALL THE REQUIREMENTS OF
 THE 2008 EDITION OF THE NEC AND BE SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 THE SUBMITTED DRAWINGS ARE VERY DIFFICULT TO
 UNDERSTAND, THEREFORE ADDITIONAL REQUIRED ITEMS MAY
 HAVE BEEN MISSED