| Date |
Text |
| 2013-11-30 19:49:41 | 550 SOUTH ROSEMARY AVENUE - SUITE #250 |
| | PERMIT #13110579 |
| | MASTER #12100361 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PLANS INDICATE "ALL DEVICES WERE REMOVED IN THE |
| | DEMOLITION AND THEY WILL BE REINSTALLED." FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | SHEET FA-1 OF THE ENGINEERED FIRE ALARM CONSTRUCTION |
| | DOCUMENTS INDICATE THE CONTRACTOR SHALL PROVIDE BATTERY |
| | CALCULATIONS AND RISER DIAGRAM; NEITHER OF WHICH WERE |
| | PROVIDED. |
| | |
| | SHEET FA-1 OF THE ENGINEERED FIRE ALARM CONSTRUCTION |
| | DOCUMENTS INDICATE THAT THE FIRE ALARM SYSTEM SHALL BE |
| | INTERFACED WITH THE SOUND SYSTEM SO THAT THE SOUND |
| | SYSTEM IS DEACTIVATED UPON ACTIVATION OF THE FIRE ALARM |
| | SYSTEM. |
| | |
| | SUBMIT A SIGNED COPY OF THE CONTRACT. THE TOTAL PERMIT |
| | JOB VALUE SHALL INCLUDE MATERIALS AND LABOR. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |