| Notes |
| Date |
Text |
| 2013-11-19 18:39:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, | | | PROVIDE CALCULATIONS. | | | | | | 3. PROVIDE INFORMATION REGARDING THE SUBSTRATE FOR THE | | | STUCCO REPAIR. THIS INFORMATION MAY BE PROVIDED ON THE | | | WINDOW PLAN OR THE INFORMATION ON THE PERMIT | | | APPLICATION (DESCRIPTION) CAN BE REVISED, FBC 107. | | | |
|