| 2014-01-13 09:54:40 | THIS PERMIT WAS CONDITIONALLY APPROVED AS FOLLOWS: | | | 1. AS PER NEC 110.26, ILLUMINATION IS REQUIRED IN FRONT | | | OF THE ELECTRICAL PANEL. | | | 2. AS PER NEC 210.62, THERE SHALL BE A SHOW WINDOW | | | OUTLET FOR EVERY 12 FT. OF SHOW WINDOW. | | | 3. AS PER NEC 600.5 THERE SHALL BE A SIGN OUTLET ABOVE | | | EVERY DOOR. | | | 4. AS PER FBC 423.17 EMERGENCY LIGHTING IS REQUIRED | | | 5. ADDITIONAL FBC-ENERGY CONSERVATION REQUIREMENTS MAY | | | EXIST, DEPENDING ON FIELD CONDITIONS NOT EXPRESSED ON | | | THESE DRAWINGS. | | | ALL WORK IS SUBJECT TO FIELD INSPECTOR'S APPROVAL |
|