2013-12-12 19:46:01THERE IS NOT SUFFICIENT DETAIL ON THE PROPOSED PLAN TO
 COMPLETE/CONDUCT AN ELECTRICAL PLAN REVIEW.
 1. THE EXISTING FLOOR PLAN SHOWS ELECT, BUT THE
 PROPOSED FLOOR PLAN DOES NOT INCLUDE ANY ELECTRIC. YOU
 NEED TO IDENTIFY WHAT IS THE EXISTING ELECTRIC AND WHAT
 IS BEING ADDED.
 2. INCLUDE ALL LIGHTING ON THE PROPOSED FLOOR PLAN FOR
 COMPLIANCE WITH NEC 110.26(D) WHICH REQUIRES THAT THERE
 BE ILLUMINATION FOR THE ELECTRICAL PANEL.
 3. YOU SHALL INCLUDE ON THE PROPOSED PLANS ALL THE
 REQUIRED EMERGENCY AND EXIT LIGHTS.
  