| Plan Review Notes For Permit 13110549 |
| Permit Number |
13110549 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-12 19:46:01 | THERE IS NOT SUFFICIENT DETAIL ON THE PROPOSED PLAN TO | | | COMPLETE/CONDUCT AN ELECTRICAL PLAN REVIEW. | | | 1. THE EXISTING FLOOR PLAN SHOWS ELECT, BUT THE | | | PROPOSED FLOOR PLAN DOES NOT INCLUDE ANY ELECTRIC. YOU | | | NEED TO IDENTIFY WHAT IS THE EXISTING ELECTRIC AND WHAT | | | IS BEING ADDED. | | | 2. INCLUDE ALL LIGHTING ON THE PROPOSED FLOOR PLAN FOR | | | COMPLIANCE WITH NEC 110.26(D) WHICH REQUIRES THAT THERE | | | BE ILLUMINATION FOR THE ELECTRICAL PANEL. | | | 3. YOU SHALL INCLUDE ON THE PROPOSED PLANS ALL THE | | | REQUIRED EMERGENCY AND EXIT LIGHTS. | | | |
|