Plan Review Notes
Plan Review Notes For Permit 13110486
Permit Number 13110486
Review Stop B
Sequence Number 1
Notes
Date Text
2013-12-03 09:52:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 REGARDING THE INSTALLATION SCHEDULE SUBMITTED:
  
 1. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHR CHARTS ON SHEETS 6&7. THE INFORMATION
 PROVIDED IS THE FASTENER; THIS INFORMATION SHOULD BE IN
 THE COLUMN LABELED "SPECIFIC ANCHOR TYPE."
  
 2. MORE THAN ONE MOUNTING TYPE HIGHLIGHTED; FOR
 INSTANCE WALL MOUNT ON SHEET 4, WHICH IS CALLED
 "SECTION 8", SEE SHEET 4 AND CHART ON SHEET 6&7), AND
 WALL MOUNT ON SHEET 3 WHICH IS "SECTION 1." EACH HAS
 ITS OWN ALLOWABLE FASTENERS AND ANCHOR SPACING, BUT
 NEITHER COMPLIES WITH THE METHOD OF INSTALLATION
 PROPOSED.
  
 THE ANCHOR SPACING FOR TAPCONS, 12" SPACING, TO
 CONCRETE, SECTION 3&4, -40PSF IS HIGHLIGHTED. NOT CLEAR
 WHAT THIS CORRELATES WITH AS ALL PROPOSED DPS ARE
 -76PSF.
  
 SEE OPENING 1. PANELMATE, -76PSF, MASONRY, REQUIRES 9
 1/2" ANCHOR SPACING.
  
 WITHOUT SPECIFIC PROPOSED CONNECTION TYPE, A DETAILED
 LIST CANNOT BE PROVIDED.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved