| Plan Review Notes For Permit 13110486 |
| Permit Number |
13110486 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-03 09:52:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | REGARDING THE INSTALLATION SCHEDULE SUBMITTED: | | | | | | 1. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE | | | WITH THE ANCHR CHARTS ON SHEETS 6&7. THE INFORMATION | | | PROVIDED IS THE FASTENER; THIS INFORMATION SHOULD BE IN | | | THE COLUMN LABELED "SPECIFIC ANCHOR TYPE." | | | | | | 2. MORE THAN ONE MOUNTING TYPE HIGHLIGHTED; FOR | | | INSTANCE WALL MOUNT ON SHEET 4, WHICH IS CALLED | | | "SECTION 8", SEE SHEET 4 AND CHART ON SHEET 6&7), AND | | | WALL MOUNT ON SHEET 3 WHICH IS "SECTION 1." EACH HAS | | | ITS OWN ALLOWABLE FASTENERS AND ANCHOR SPACING, BUT | | | NEITHER COMPLIES WITH THE METHOD OF INSTALLATION | | | PROPOSED. | | | | | | THE ANCHOR SPACING FOR TAPCONS, 12" SPACING, TO | | | CONCRETE, SECTION 3&4, -40PSF IS HIGHLIGHTED. NOT CLEAR | | | WHAT THIS CORRELATES WITH AS ALL PROPOSED DPS ARE | | | -76PSF. | | | | | | SEE OPENING 1. PANELMATE, -76PSF, MASONRY, REQUIRES 9 | | | 1/2" ANCHOR SPACING. | | | | | | WITHOUT SPECIFIC PROPOSED CONNECTION TYPE, A DETAILED | | | LIST CANNOT BE PROVIDED. | | | | | | |
|