| Plan Review Notes For Permit 13110447 |
| Permit Number |
13110447 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-27 11:50:08 | THE EQUIPMENT IN QUESTION WILL NOT BE FLOATING IN AIR, | | | THEREFORE PLEASE PROVIDE /INCLUDE THE METHOD OF SUPPORT | | | BEING USED. | | | THERE IS NO MENTION OF ANY LOADS BEING ATTACHED TO THIS | | | PANEL, PLEASE INDICATE WHAT WILL BE ATTACHED TO THE | | | TEMPORARY SERVICE POLE, MAKING SURE THAT ALL OUTLETS | | | ARE GFCI PROTECTED AND COMPLY WITH NEC 406. | | | IF THE SERVICE DROP SERVING THIS POLE IS LOCATED ACROSS | | | THE STREET, PROPER CLEARANCES WILL BE REQUIRED. | | | |
|