| Date |
Text |
| 2013-12-13 12:12:03 | 1224 OKEECHOBEE ROAD |
| | PERMIT #13110415 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL COMPLY WITH 2010 EDITION OF THE FLORIDA |
| | FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF |
| | BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | THE TOTAL PERMIT JOB VALUE NEEDS TO INCLUDE MATERIALS |
| | AND LABOR. |
| | |
| | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. |
| | |
| | INDICATE IF THIS GARAGE WILL BE USED FOR "MAJOR" |
| | REPAIRS OR "MINOR" REPAIRS. (NFPA 30A - 3.3.12 REPAIR |
| | GARAGES: "MAJOR REPAIR GARAGE" A BUILDING OR PORTIONS |
| | OF A BUILDING WHERE MAJOR REPAIRS, SUCH AS ENGINE |
| | OVERHAULS, PAINTING, BODY AND FENDER WORK, AND REPAIRS |
| | THAT REQUIRE DRAINING OF THE MOTOR VEHICLE FUEL TANK |
| | ARE PERFORMED ON MOTOR VEHICLES, INCLUDING ASSOCIATED |
| | FLOOR SPACE USED FOR OFFICES, PARKING, OR SHOWROOMS. |
| | "MINOR REPAIR GARAGE" A BUILDING OR PORTIONS OF A |
| | BUILDING USED FOR LUBRICATION, INSPECTION, AND MINOR |
| | AUTOMOTIVE MAINTENANCE WORK, SUCH AS ENGINE TUNE-UPS, |
| | REPLACEMENT OF PARTS, FLUID CHANGES (E.G., OIL, |
| | ANTIFREEZE, TRANSMISSION FLUID, BRAKE FLUID, AIR |
| | CONDITIONING REFRIGERANTS, ETC.), BRAKE SYSTEM REPAIRS, |
| | TIRE ROTATION, AND SIMILAR ROUTINE MAINTENANCE WORK, |
| | INCLUDING ASSOCIATED FLOOR SPACE USED FOR OFFICES, |
| | PARKING, OR SHOWROOMS.) |
| | |
| | REPAIR GARAGES USED FOR REPAIR OF VEHICLE ENGINE FUEL |
| | SYSTEMS FUELED BY NON-ODORIZED GASES, SUCH AS HYDROGEN |
| | AND NON-ODORIZED LNG/CNG, SHALL BE PROVIDED WITH AN |
| | APPROVED FLAMMABLE GAS DETECTION SYSTEM. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, |
| | OCCUPANT LOADS, FIRE RATED WALLS, EXITS, EXIT SIGNS, |
| | EGRESS LIGHTING, EMERGENCY LIGHTING, TRAVEL DISTANCES, |
| | COMMON PATH OF TRAVEL ETC. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING |
| | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT |
| | MORE THAN ONE RELEASING OPERATION. THE RELEASING |
| | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. |
| | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING |
| | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT |
| | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO |
| | OPERATE. |
| | |
| | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | AT THIS TIME A THOROUGH A COMPLETE PLAN REVIEW CANNOT |
| | BE COMPLETED AT THIS TIME DUE TO A LACK OF PLAN |
| | INFORMATION. ADDITIONAL COMMENTS MAY BE GENERATED AFTER |
| | ADDITIONAL INFORMATION IS SUBMITTED. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |