 PERMIT #13110415
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL COMPLY WITH 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 THE TOTAL PERMIT JOB VALUE NEEDS TO INCLUDE MATERIALS
 AND LABOR.
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 INDICATE IF THIS GARAGE WILL BE USED FOR "MAJOR"
 REPAIRS OR "MINOR" REPAIRS. (NFPA 30A - 3.3.12 REPAIR
 GARAGES: "MAJOR REPAIR GARAGE" A BUILDING OR PORTIONS
 OF A BUILDING WHERE MAJOR REPAIRS, SUCH AS ENGINE
 OVERHAULS, PAINTING, BODY AND FENDER WORK, AND REPAIRS
 THAT REQUIRE DRAINING OF THE MOTOR VEHICLE FUEL TANK
 ARE PERFORMED ON MOTOR VEHICLES, INCLUDING ASSOCIATED
 FLOOR SPACE USED FOR OFFICES, PARKING, OR SHOWROOMS.
 "MINOR REPAIR GARAGE" A BUILDING OR PORTIONS OF A
 BUILDING USED FOR LUBRICATION, INSPECTION, AND MINOR
 AUTOMOTIVE MAINTENANCE WORK, SUCH AS ENGINE TUNE-UPS,
 REPLACEMENT OF PARTS, FLUID CHANGES (E.G., OIL,
 ANTIFREEZE, TRANSMISSION FLUID, BRAKE FLUID, AIR
 CONDITIONING REFRIGERANTS, ETC.), BRAKE SYSTEM REPAIRS,
 TIRE ROTATION, AND SIMILAR ROUTINE MAINTENANCE WORK,
 INCLUDING ASSOCIATED FLOOR SPACE USED FOR OFFICES,
 PARKING, OR SHOWROOMS.)
  
 REPAIR GARAGES USED FOR REPAIR OF VEHICLE ENGINE FUEL
 SYSTEMS FUELED BY NON-ODORIZED GASES, SUCH AS HYDROGEN
 AND NON-ODORIZED LNG/CNG, SHALL BE PROVIDED WITH AN
 APPROVED FLAMMABLE GAS DETECTION SYSTEM.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXITS, EXIT SIGNS,
 EGRESS LIGHTING, EMERGENCY LIGHTING, TRAVEL DISTANCES,
 COMMON PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 AT THIS TIME A THOROUGH A COMPLETE PLAN REVIEW CANNOT
 BE COMPLETED AT THIS TIME DUE TO A LACK OF PLAN
 INFORMATION. ADDITIONAL COMMENTS MAY BE GENERATED AFTER
 ADDITIONAL INFORMATION IS SUBMITTED.
  