| Plan Review Notes For Permit 13110415 |
| Permit Number |
13110415 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-08 19:13:16 | NO ELECTRICAL PLANS WERE SUBMITTED FOR REVIEW. YOU | | | SHALL SUBMIT A COMPLETE SET OF ELECTRICAL DRAWINGS | | | CONTAINING THE FOLLOWING FOR REVIEW: | | | AS PER FBC-B SECTION 107.3.5 MINIMUM PLAN REVIEW | | | CRITERIA IS REQUIRED. | | | 1.A SINGLE LINE RISER DIAGRAM INDICATING: | | | A) ELECTRIC SERVICE SIZE AND LOCATION OF DISCONNECTS | | | AND ANY SUBPANELS. | | | B) GROUNDING | | | 2. ELECTRICAL PANEL SCHEDULE ALONG WITH A DESCRIPTION | | | OF THE EQUIPMENT IN USE.BEING INSTALLED | | | 3) LOAD CALCULATIONS | | | 4) BRANCH CIRCUIT SIZE AND OVER CURRENT PROTECTION | | | 5) FLOOR PLANS INDICATING LOCATION OF ELECTRICAL | | | PANELS, GENERAL LIGHTING OUTLETS AND SWITCHES, | | | EMERGENCY AND REQUIRED EXIT LIGHTS |
|