| 2013-11-27 13:08:49 | BUILDING PLAN REVIEW |
| | PERMIT: 13110415 |
| | ADD: 1224 OKEECHOBEE RD |
| | CONT: FIRST FLORIDA CONTRACTORS |
| | TEL: (351) 521-7145 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 27/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: |
| | 107.3.5.1 COMMERCIAL BUILDINGS,107.3.5.1.1 BUILDING : |
| | A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | FLOOR PLAN |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | B) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING |
| | REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | C) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | SOIL CONDITIONS/ANALYSIS |
| | TERMITE PROTECTION |
| | D) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | E) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | |
| | 3) THE PERMIT VALUATION FOR THIS PROJECT IS LISTED AS |
| | $49,886.00, THIS VALUE IS EXTERMLY LOW. W P B |
| | ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON |
| | BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND |
| | PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A |
| | FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | TYPE V-B CONSTRUCTION |
| | OCCUPANCY TYPE S-1 2100 SQ FT X $56.71= $ 119,091.00 |
| | CALCULATED VALUE, THIS VALUE WILL BE ASSESSED TO THIS |
| | PERMIT FOR PERMIT FEES OWED. |
| | |
| | 4) ELEVATION SHEET 1OF 3 SHEETS TITLEBLOCK HEADING |
| | METAL STRUCTURES LLC: |
| | 4A) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | |
| | 4B) PROVIDE LOCATION OF PROJECT ON PLANS, ADDRESS. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION. |
| | |
| | 5) DISCREPANCY IN PLANS, ELEVATION SHEET 1OF 3 SHEETS |
| | INDICATES AN B-EXPOSURE WHILE THE ENGINEERED PLAN FROM |
| | P.E. MICHAEL ROBINSON INDICATES A C-EXPOSURE. I AGREE |
| | WITH THE ENGINEER OF RECORD THIS LOCATION IS CONSIDERED |
| | A C EXPOSURE BECAUSE OF SURFACE ROUGHNESS C FBC-B |
| | 1609.4.2. |
| | |
| | 6) BOTH THE ELEVATION SHEET AND SHEET 1 OF 2 ENGINEERED |
| | SHEET INDICATES THE BUILDING CATEGORY AS A BUILDING |
| | CATEGORY I WITH AN IMPORTANCE FACTOR OF 0.77. THE TITLE |
| | BLOCK INDICATES THIS TO BE A GARAGE/ SHED THE BUILDING |
| | OFFICIAL HAS REVIEWED THE SIZE AND USAGE OF THIS |
| | BUILDING AND HAS DETERMINED THE IMPORTANCE FACTOR IS |
| | LOW AND SHOULD BE A CATEGORY II BUILDING AND A FACTOR |
| | OF 1.0. THIS WILL AFFECT THE PRESSURES OF THIS BUILDING |
| | AS WELL AS THE SIZE OF THE FOUNDATION. |
| | |
| | 7) PLEASE PROVIDE COMPLIANCE WITH 2210.1 GENERAL. |
| | THE DESIGN AND INSTALLATION OF STRUCTURAL MEMBERS AND |
| | NONSTRUCTURAL MEMBERS UTILIZED IN COLD-FORMED STEEL |
| | LIGHT-FRAME CONSTRUCTION WHERE THE SPECIFIED MINIMUM |
| | BASE STEEL THICKNESS IS BETWEEN 0.0179 INCHES (0.455 |
| | MM) AND 0.1180 INCHES (2.997 MM) SHALL BE IN ACCORDANCE |
| | WITH AISI S200 AND SECTIONS 2210.2 THROUGH 2210.7, AS |
| | APPLICABLE. |
| | |
| | 2210.2 HEADER DESIGN. |
| | HEADERS, INCLUDING BOX AND BACK-TO-BACK HEADERS, AND |
| | DOUBLE AND SINGLE L-HEADERS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH AISI S212 OR AISI S100. |
| | |
| | 2210.3 TRUSSES. |
| | |
| | 2210.3.1 DESIGN. |
| | COLD-FORMED STEEL TRUSSES SHALL BE DESIGNED IN |
| | ACCORDANCE WITH AISI S214, SECTIONS 2210.3.1 THROUGH |
| | 2210.3.5 AND ACCEPTED ENGINEERING PRACTICE. |
| | |
| | 2210.3.2 TRUSS DESIGN DRAWINGS. |
| | THE TRUSS DESIGN DRAWINGS SHALL CONFORM TO THE |
| | REQUIREMENTS OF SECTION B2.3 OF AISI S214 AND SHALL BE |
| | PROVIDED WITH THE SHIPMENT OF TRUSSES DELIVERED TO THE |
| | JOB SITE. THE TRUSS DESIGN DRAWINGS SHALL INCLUDE THE |
| | DETAILS OF PERMANENT INDIVIDUAL TRUSS MEMBER |
| | RESTRAINT/BRACING IN ACCORDANCE WITH SECTION B6(A) OR |
| | B6(C) OF AISI S214 WHERE THESE METHODS ARE UTILIZED TO |
| | PROVIDE RESTRAINT/BRACING. |
| | |
| | 2210.3.5 TRUSS QUALITY ASSURANCE. |
| | TRUSSES NOT PART OF A MANUFACTURING PROCESS THAT |
| | PROVIDES REQUIREMENTS FOR QUALITY CONTROL DONE UNDER |
| | THE SUPERVISION OF A THIRD-PARTY QUALITY CONTROL |
| | AGENCY, SHALL BE MANUFACTURED IN COMPLIANCE WITH |
| | SECTIONS 1704.2 AND 1704.3, AS APPLICABLE. |
| | |
| | 2210.4 WALL STUD DESIGN. |
| | WALL STUDS SHALL BE DESIGNED IN ACCORDANCE WITH EITHER |
| | AISI S211 OR AISI S100. |
| | |
| | 2210.5 FLOOR AND ROOF SYSTEM DESIGN. |
| | FRAMING FOR FLOOR AND ROOF SYSTEMS IN BUILDINGS SHALL |
| | BE DESIGNED IN ACCORDANCE WITH EITHER AISI S210 OR AISI |
| | S100. |
| | |
| | 2210.6 LATERAL DESIGN. |
| | LIGHT-FRAME SHEAR WALLS, DIAGONAL STRAP BRACING THAT IS |
| | PART OF A STRUCTURAL WALL AND DIAPHRAGMS USED TO RESIST |
| | WIND AND OTHER IN-PLANE LATERAL LOADS SHALL BE DESIGNED |
| | IN ACCORDANCE WITH AISI S213. |
| | |
| | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | FL 15870 SWING GLASS DOOR. NOTE THIS STATE APPROVAL |
| | DOES NOT HAVE ANY CONNECTIONS TO STEEL WITHIN THE |
| | PRODUCT APPROVAL. |
| | NOA 12-0322.06 EXPIRED 4/19/2013 ROLL UP GARAGE DOOR |
| | (B)) PANEL WALLS |
| | (C): WALL LOUVERS,: NO PRODUCT APPROVAL WAS SUBMITTED. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES PLEASE IDENTIFY |
| | WHICH SUB-SYSTEM IS TO BE INSTALLED. PLEASE ALSO |
| | PROVIDE THE AE EVALUATION REPORT. PLEASE NOTE IF THE |
| | REPORT REQUIRES COMPLIANCE WITH 1507.4.1 DECK |
| | REQUIREMENTS. PLEASE ALSO PROVIDE MANUFACTURES |
| | SPECIFICATIONS THAT THE ROOFING MATERIAL CAN BE APPLIED |
| | HORIZONTALLY AS DEPICTED SHEET 1 OF 2 . NORMALLY ON |
| | STEEL BUILDINGS THERE ARE HORIZONTAL PURLINS ON BOTH |
| | THE WALL AS WELL AS THE ROOF SYSTEM. THE ELEVATION |
| | DRAWING SHOWA THE ROOF PANELS BEING APPLIED VERTICALLY |
| | THE PLANS DO NOT INDICATE THE USE OF PURLINS OR SOLID |
| | ROOF SHEATHING, HOW WILL THE GABLE WALL OVER HANGS BE |
| | STRUCTURALLY ATTACHED. |
| | |
| | 10) PLEASE PROVIDE CALCULATIONS FOR THE MOMMENT OF |
| | OVERTURNING FOR THE STRUCTURE ITSELF IT SEAMS THE |
| | FOUNDATION IS LIGHT, SINCE THE PLANS INDICATE THERE IS |
| | A EXISTING SLAB. |
| | |
| | 11) FBC-B 406.6.3 VENTILATION. REPAIR GARAGES SHALL BE |
| | MECHANICALLY VENTILATED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, MECHANICAL. THE VENTILATION SYSTEM SHALL |
| | BE CONTROLLED AT THE ENTRANCE TO THE GARAGE. |
| | |
| | 406.6.4 FLOOR SURFACE. REPAIR GARAGE FLOORS SHALL BE OF |
| | CONCRETE OR SIMILAR NONCOMBUSTIBLE AND NONABSORBENT |
| | MATERIALS. |
| | EXCEPTION: SLIP-RESISTANT, NONABSORBENT, INTERIOR FLOOR |
| | FINISHES HAVING A CRITICAL RADIANT FLUX NOT MORE THAN |
| | 0.45 W/CM2, AS DETERMINED BY NFPA 253, SHALL BE |
| | PERMITTED. |
| | |
| | [F] 406.6.6 GAS DETECTION SYSTEM. REPAIR GARAGES USED |
| | FOR REPAIR OF VEHICLES FUELED BY NONODORIZED GASES, |
| | SUCH AS HYDROGEN AND NONODORIZED LNG, SHALL BE PROVIDED |
| | WITH A FLAMMABLE GAS DETECTION SYSTEM. |
| | |
| | [F] 406.6.6.1 SYSTEM DESIGN. THE FLAMMABLE GAS |
| | DETECTION SYSTEM SHALL BE LISTED OR APPROVED AND SHALL |
| | BE CALIBRATED TO THE TYPES OF FUELS OR GASES USED BY |
| | VEHICLES TO BE REPAIRED. GAS DETECTORS OR SENSORS SHALL |
| | BE LISTED IN ACCORDANCE WITH UL 2075 AND SHALL INDICATE |
| | THE GASES THEY ARE INTENDED TO DETECT. THE GAS |
| | DETECTION SYSTEM SHALL BE DESIGNED TO ACTIVATE WHEN THE |
| | LEVEL OF FLAMMABLE GAS EXCEEDS 25 PERCENT OF THE LOWER |
| | EXPLOSIVE LIMIT. GAS DETECTION SHALL ALSO BE PROVIDED |
| | IN LUBRICATION OR CHASSIS REPAIR PITS OF GARAGES USED |
| | FOR REPAIRING NONODORIZED LNG-FUELED VEHICLES. |
| | |
| | [F] 406.6.6.2 OPERATION. |
| | ACTIVATION OF THE GAS DETECTION SYSTEM SHALL RESULT IN |
| | ALL OF THE FOLLOWING: |
| | 1. INITIATION OF DISTINCT AUDIBLE AND VISUAL ALARM |
| | SIGNALS IN THE REPAIR GARAGE. |
| | 2. DEACTIVATION OF ALL HEATING SYSTEMS LOCATED IN THE |
| | REPAIR GARAGE. |
| | 3. ACTIVATION OF THE MECHANICAL VENTILATION SYSTEM, |
| | WHERE THE SYSTEM IS INTERLOCKED WITH GAS DETECTION. |
| | |
| | [F] 406.6.6.3 FAILURE OF THE GAS DETECTION SYSTEM. |
| | FAILURE OF THE GAS DETECTION SYSTEM SHALL RESULT IN THE |
| | DEACTIVATION OF THE HEATING SYSTEM, ACTIVATION OF THE |
| | MECHANICAL VENTILATION SYSTEM WHEN THE SYSTEM IS |
| | INTERLOCKED WITH THE GAS DETECTION SYSTEM AND CAUSE A |
| | TROUBLE SIGNAL TO SOUND IN AN APPROVED LOCATION. |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |