2013-12-12 11:31:42THE FOLLOWING ITEMS SHALL BE ADDRESSED AND CORRECTED
 ACCORDINGLY:
 (1) FOR THE DAY CARE CONVERSION
 1. THE SUBMITTED DRAWINGS DO NOT SHOW THE LOCATION OF
 THE ELECTRICAL PANEL.
 2. THE REQUIRED DISCONNECT FOR THE WATER HEATER IS NOT
 SHOWN.
 3. AN ELECTRICAL SERVICE RISER DIAGRAM SHALL BE
 PROVIDED W/A PANEL SCHEDULE.
 4. THE FBC AS WELL AS THE NEC HAVE SPECIFIC
 REQUIREMENTS FOR LIGHTING OF A DAY CARE CENTER. A
 LIGHTING SCHEDULE/PLANS SHALL BE PROVIDED.
 5. EMERGENCY AND EXIT LIGHTING SHALL BE INSTALLED
 6. COMPLIANCE W/THE FBC-ENERGY CONSERVATION CODE IS
 REQUIRED. THUS LIGHTING CONTROL MUST BE INCLUDED.
  
 (2) THRIFT STORE BUILD OUT
 1. AN ELECTRICAL SERVICE RISER DIAGRAM, ALONG WITH A
 PANEL SCHEDULE AND LOAD CALCS SHALL BE PROVIDED.
 2. A FLOOR PLAN SHOWING THE EXISTING ELECTRIC ALONG
 WITH THE LOCATION OF THE ELECTRICAL PANEL.
 3. THE FLOOR PLANS SHALL INCLUDE THE REQUIRED EMERGENCY
 & EXIT LIGHTS AS PER CODE.
 4. COMPLIANCE WITH THE FBC-ENERGY CONSERVATION CODE
 SHALL BE REQUIRED, THEREFORE SPECIFIC LIGHTING
 REQUIREMENTS AND CONTROL ARE REQUIRED.
  
 THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH
 LIST FOR THE DESIGNER, THEREFORE ADDITIONAL
 REQUIREMENTS MAY EXIST.
  