| 2013-12-12 11:31:42 | THE FOLLOWING ITEMS SHALL BE ADDRESSED AND CORRECTED |
| | ACCORDINGLY: |
| | (1) FOR THE DAY CARE CONVERSION |
| | 1. THE SUBMITTED DRAWINGS DO NOT SHOW THE LOCATION OF |
| | THE ELECTRICAL PANEL. |
| | 2. THE REQUIRED DISCONNECT FOR THE WATER HEATER IS NOT |
| | SHOWN. |
| | 3. AN ELECTRICAL SERVICE RISER DIAGRAM SHALL BE |
| | PROVIDED W/A PANEL SCHEDULE. |
| | 4. THE FBC AS WELL AS THE NEC HAVE SPECIFIC |
| | REQUIREMENTS FOR LIGHTING OF A DAY CARE CENTER. A |
| | LIGHTING SCHEDULE/PLANS SHALL BE PROVIDED. |
| | 5. EMERGENCY AND EXIT LIGHTING SHALL BE INSTALLED |
| | 6. COMPLIANCE W/THE FBC-ENERGY CONSERVATION CODE IS |
| | REQUIRED. THUS LIGHTING CONTROL MUST BE INCLUDED. |
| | |
| | (2) THRIFT STORE BUILD OUT |
| | 1. AN ELECTRICAL SERVICE RISER DIAGRAM, ALONG WITH A |
| | PANEL SCHEDULE AND LOAD CALCS SHALL BE PROVIDED. |
| | 2. A FLOOR PLAN SHOWING THE EXISTING ELECTRIC ALONG |
| | WITH THE LOCATION OF THE ELECTRICAL PANEL. |
| | 3. THE FLOOR PLANS SHALL INCLUDE THE REQUIRED EMERGENCY |
| | & EXIT LIGHTS AS PER CODE. |
| | 4. COMPLIANCE WITH THE FBC-ENERGY CONSERVATION CODE |
| | SHALL BE REQUIRED, THEREFORE SPECIFIC LIGHTING |
| | REQUIREMENTS AND CONTROL ARE REQUIRED. |
| | |
| | THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH |
| | LIST FOR THE DESIGNER, THEREFORE ADDITIONAL |
| | REQUIREMENTS MAY EXIST. |
| | |