| Date |
Text |
| 2013-11-22 17:18:02 | BUILDING PLAN REVIEW |
| | PERMIT: 13110391 |
| | ADD: 1700 N DIXIE HWY |
| | CONT: LIBERTY SOUTH CONSTRUCTION SERVICES |
| | TEL: (561)282-3019 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY NOV. 22/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE ADDITIONAL INFORMATION ON PROJECT. |
| | THE COVERSHEET MAKES IT APPEAR THERE IS ROOM BETWEEN |
| | THESE TWO BUILDINGS WHERE AS THE ARIAL VIEW OF THIS |
| | LOT, IT APPEARS THIS IS ONE BUILDING THAT WAS BUILT |
| | WITH AN ADDITION. PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION TO BE ABLE TO DETERMINE CODE COMPLIANCE. |
| | ONE BUILDING OR TWO, IS THERE A 4 HOUR FIRE WALL |
| | BETWEEN THE TWO UNITS, IS THIS ONE BUILDING AND TO BE |
| | CONSIDERED A MIXED OCCUPANCY. |
| | |
| | PROVIDE THIS INFORMATION FOR BOTH BUILDINGS: |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION, |
| | 107. 3.5.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 1. SITE REQUIREMENTS: |
| | PARKING |
| | SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS |
| | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | 11.INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | |
| | BUILDING # 1 |
| | 2) SHOW COMPLIANCE WITH :FBC-B 436.1.2 |
| | WHERE DAY CARE OCCUPANCIES WITH CLIENTS 24 MONTHS OR |
| | LESS IN AGE OR INCAPABLE OF SELF-PRESERVATION ARE |
| | LOCATED ONE OR MORE STORIES ABOVE THE LEVEL OF EXIT |
| | DISCHARGE OR WHERE DAY CARE OCCUPANCIES ARE LOCATED TWO |
| | OR MORE STORIES ABOVE THE LEVEL OF EXIT DISCHARGE, |
| | SMOKE BARRIERS SHALL BE PROVIDED TO DIVIDE SUCH STORIES |
| | INTO A MINIMUM OF TWO SMOKE COMPARTMENTS. THE SMOKE |
| | BARRIERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 709 BUT SHALL NOT BE REQUIRED TO HAVE A |
| | FIRE-RESISTANCE RATING. |
| | |
| | 436.2 CLOSET DOORS. |
| | EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN |
| | OPEN THE DOOR FROM INSIDE THE CLOSET. |
| | |
| | 436.3 BATHROOM DOORS. |
| | EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO PERMIT |
| | OPENING OF THE LOCKED DOOR FROM THE OUTSIDE IN AN |
| | EMERGENCY. THE OPENING DEVICE SHALL BE READILY |
| | ACCESSIBLE TO THE STAFF. |
| | |
| | 3) 436.6 PROTECTION FROM HAZARDS. ROOMS OR SPACES FOR |
| | THE STORAGE, PROCESSING OR USE OF MATERIALS SPECIFIED |
| | BELOW SHALL BE PROTECTED IN ACCORDANCE WITH THE |
| | FOLLOWING: |
| | 436.6.1 |
| | THE FOLLOWING ROOMS OR SPACES SHALL BE SEPARATED FROM |
| | THE REMAINDER OF THE BUILDING BY FIRE BARRIERS HAVING A |
| | FIRE RESISTANCE RATING OF NOT LESS THAN 1-HOUR OR SHALL |
| | BE PROTECTED BY AN APPROVED AUTOMATIC EXTINGUISHING |
| | SYSTEM. |
| | 1. BOILER AND FURNACE ROOMS. |
| | EXCEPTION: ROOMS ENCLOSING ONLY AIR-HANDLING EQUIPMENT. |
| | 2. ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE |
| | SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE BUILDING |
| | OFFICIAL. |
| | 3. ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS |
| | MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN |
| | QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS. |
| | 4. JANITOR CLOSETS. |
| | EXCEPTION: DOORS TO JANITOR CLOSETS SHALL BE PERMITTED |
| | TO HAVE VENTILATING LOUVERS WHERE THE SPACE IS |
| | PROTECTED BY AUTOMATIC SPRINKLERS. |
| | |
| | 4) 436.6.2 THE FOLLOWING ROOMS OR SPACES SHALL BE |
| | SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE |
| | BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT LESS |
| | THAN 1 HOUR AND SHALL BE PROTECTED BY AN APPROVED |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEM. |
| | 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| | COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING |
| | OFFICIAL. |
| | 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| | HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS |
| | IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS. |
| | |
| | 5) 436.7 DETECTION AND ALARM SYSTEMS. |
| | DAY CARE OCCUPANCIES SHALL BE PROVIDED WITH A FIRE |
| | ALARM SYSTEM IN ACCORDANCE WITH SECTION 907 AND THIS |
| | SECTION. |
| | 436.7.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE BY MANUAL MEANS AND BY OPERATION OF ANY |
| | REQUIRED SMOKE DETECTORS AND REQUIRED SPRINKLER |
| | SYSTEMS. |
| | 436.7.1.1 OCCUPANT NOTIFICATION SIGNALS SHALL BE |
| | AUDIBLE AND VISUAL SIGNALS IN ACCORDANCE WITH NFPA 72 |
| | AND THE FLORIDA BUILDING CODE, ACCESSIBILITY. THE |
| | GENERAL EVACUATION ALARM SIGNAL SHALL OPERATE |
| | THROUGHOUT THE ENTIRE BUILDING. |
| | 436.7.2 DETECTION. |
| | A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN |
| | EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN |
| | THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE |
| | OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN |
| | LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY |
| | CARE OCCUPANCY. |
| | |
| | 6) 1029.4.1 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE |
| | FEET (23.2 M2) IN EDUCATIONAL OCCUPANCIES USED FOR |
| | CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR NORMALLY |
| | SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM OR SPACE |
| | NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN |
| | BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE NOT LESS |
| | THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT |
| | COMPLIES WITH THE FOLLOWING: |
| | |
| | 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH, |
| | 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53 |
| | M2) IN AREA. |
| | 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING |
| | DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE |
| | THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR. |
| | EXCEPTIONS: |
| | 1. BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION 903.3.1.1. |
| | 2. WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| | TO THE OUTSIDE OF THE BUILDING. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | _______________________________________________________ |
| | ______________ |
| | |
| | BUILDING # 2 |
| | |
| | 8) SHEET A-005.00 INDICATES WITH A ELEVATION NEW PAIR |
| | OF DOORS, THE DOOR SCHEDULE INDICATES DOOR INDENTIFIED |
| | AS # 2 TO BE A SINGLE 2'-10" DOOR, A 1 1/2 HOUR RATING |
| | & FRAME. A PAIR OF DOUBLE DOORS 2 X 2'-10" DOORS AND |
| | FRAME WILL NOT FIT INTO A 5'-8" OPENING (OLD WINDOW) AS |
| | INDICATED ON THE COVER SHEET. |
| | |
| | 9) THIS SAME ELEVATION DETAIL INDICATES THERE WAS A |
| | CLEARSTORY BE REMOVED AND A NEW STEEL LINTEL TO BE |
| | INSTALLED. THE PLANS DO NOT INDICATE WHAT IS TO BE USED |
| | TO FILL IN THE AREA ABOVE THE STEEL LINTEL. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS LINTELS, |
| | |
| | 10) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 11.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 11.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 11.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 11.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 11.5) COMPONENTS & CLADDING PRESSURES POSITVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 12) THIS BUILDING IS BEING CONVERTED FROM STORAGE TO A |
| | THRIFT SHOP, THE PLANS DO NOT PROVIDE ANY INFORMATION |
| | ON CODE COMPLIANCE FOR: 904.4 SALES AND SERVICE |
| | COUNTERS. |
| | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| | SERVICE COUNTER TOP. |
| | |
| | EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A |
| | COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A |
| | REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK |
| | STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL |
| | BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION |
| | WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH |
| | 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR |
| | GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF |
| | THE COUNTER. |
| | |
| | |
| | |
| | FIGURE 904.4 (EXCEPTION) |
| | ALTERATION OF SALES AND SERVICE COUNTERS |
| | |
| | 904.4.1 PARALLEL APPROACH. |
| | A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915 |
| | MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| | ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| | FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915 |
| | MM) MINIMUM LENGTH OF COUNTER. |
| | |
| | EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS |
| | THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER |
| | SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE |
| | THE FINISH FLOOR. |
| | |
| | 904.4.2 FORWARD APPROACH. |
| | A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760 |
| | MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| | SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH |
| | 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| | FOR A FORWARD APPROACH TO THE COUNTER. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |