| Date |
Text |
| 2013-11-18 09:53:07 | MECHANICAL PLAN REVIEW |
| | PERMIT: 13110367 |
| | ADD: 1771 PALM BEACH LAKES # W311 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)373-3902 CONTACT KARI NEVELLE |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON./ NOV. 18/ 2013 |
| | ACTION:MECHANICAL PROVISO |
| | MECHANICAL APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | |
| | 1) DISCREPANCY IN PLANS M-102 DUCT INDENTIFIED AS SD-2 |
| | IS IDENTIFIED AS A 6 INCH DIAMETER DUCT WHEREAS SHEET |
| | M101 IDENTIFIES IT AS A 8 " DIAMETER DUCT. 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUESTED, DISCREPANCY. |
| | |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |