| Plan Review Notes For Permit 13110342 |
| Permit Number |
13110342 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-02-10 07:28:53 | APPROVED WITH EXCEPTION, REVISION REQUIRED | | | SUBMIT 2 COPIES OF CORRECTED ENERGY CALCULATIONS THAT | | | MATCH PLANS. | | | | | | NOTE: | | | THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA, DESIGNATED FLOOD ZONE A5. THE MINIMUM ELEVATION | | | IS 7 FEET BFE PLUS THE ADDITIONAL 6" OF FREEBOARD | | | REQUIRED BY CITY ORDINANCE. BASED ON CITY BUILDING | | | DEPARTMENT RECORDS THE CUMULATIVE TOTAL COSTS OF WORK | | | ON THIS BUILDING INCLUDING $32,000.00 FOR THE PROPOSED | | | WORK IS $ 105,889.00. THE CONTRACTOR SUBMITTED AN | | | APPRAISAL FROM CHARLEEN MCMANUS, SRA, OF ANDERSON & | | | CARR, INC. STATING THE MARKET VALUE OF THE BUILDING | | | IMPROVEMENTS TO BE $ 320,000.00. BECAUSE THE TOTAL OF | | | PREVIOUS IMPROVEMENTS AND THE PROPOSED WORK IS LESS | | | THAN 50 PERCENT OF THE MARKET VALUE, THIS IS NOT | | | CONSIDERED A SUBSTANTIAL IMPROVEMENT. ACCORDING TO THE | | | PROPERTY APPRAISER'S RECORDS THE STRUCTURE WAS BUILT IN | | | 1935 AND HAS HAD NO SUBSTANTIAL IMPROVEMENTS PRIOR TO | | | THE DATE OF THE INITIAL FIRM (MARCH 1, 1979) . | | | THEREFORE THIS IS BUILDING IS CONSIDERED TO BE | | | PRE-FIRM. BASED ON TABLE 6-1A IN FEMA PUBLICATION P-758 | | | NEITHER THE LATERAL ADDITION NOR THE REMODEL IS | | | REQUIRED TO COMPLY WITH NFIP REQUIREMENTS FOR NEW | | | CONSTRUCTION. |
|